Iai-america ERC2 Manual de usuario Pagina 102

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 138
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 101
92
6. Parameter Settings
83
z Silent interval multiplication factor (No.45 SIVM)
It is applied to controllers of RS485 serial communication type.
If specified, this parameter defines the multiplication factor to be applied to the silent interval time for delimiter
judgment in the RTU mode.
The default setting is the communication time corresponding to 3.5 characters in accordance with the Modbus
specification.
This setting need not be changed for normal operations performed with a PC or teaching pendant.
If the scan time of the PLC is not optimal and the character transmission interval exceeds the silent interval, the
silent interval time can be extended using parameter No. 45.
The minimum setting unit is “1 [time],” while the input range is “0 to 10.” If “0” is set, no multiplication factor is
applied.
Vista de pagina 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 137 138

Comentarios a estos manuales

Sin comentarios