33
4. Wiring
4.2.2 Wiring the Power Supply/Emergency-Stop Switch
(1) Wiring the power supply
To connect multiple controllers, provide a relay terminal block.
Use a power cable satisfying the following specifications:
Item Specification
Applicable wire length
Single wire: 1.0 / Stranded: 0.8 mm
2
, AWG size 18, (copper wire)
Stripped wire length 10 mm
Temperature rating of
isolated sheath
60qC or above
* Use a flathead screwdriver with a blade tip of approx. 2.6 mm to push in the wire.
S1
S2
MPI
MPO
24V
0V
EMG-
24V
0V
FG
Input power supply
24 VDC
(2 A max. per controller)