(2) I/O Signal Allocation for each Axis
The I/O signals for each axis consists of 4 words for each I/O bit register.
z The control signals and status signals are ON/OFF signals in units of bit.
z The target position and current position are expressed using 2-word (32 bits) binary data. The
figures from –999999 to +999999 (Unit: 0.01mm) can be set in PLC. However, set the position data
within the soft stroke range (0 to effective stroke length)
for the actuator in question.
z The specified position No. and completed position No. are expressed using 1-word (16 bits) binary
data. The figures from 0 to 767 can be set in PLC. However, set the position No. for which the
operation conditions have been set in advance using the personal computer software or teaching
pendant.
PLC Output
Address (* “n” shows the head register address per each axis).
one word = 16 bits
RWw (n+0) b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Target
Position
(Slave Word)
RWw (n+1) b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Target
Position
(Host Word)
When the target position is shown using the negative figure, it is expressed using the
complement of 2.
one word = 16 bits
RWw (n+2) b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Command
position
No.
PC512
PC256
PC128
PC64
PC32
PC16
PC8
PC4
PC2
PC1
RWw (n+3) b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Control
signal
BKRL
RMOD
PMOD
MODE
PWRT
JOG+
JOG-
JVEL
JISL
SON
RES
STP
HOME
CSTR